Ecoinformatics site parent site of Partnership for Biodiversity Informatics site parent site of REAP - Home


 

 

 



Terrestrial Use Case Hardware

Difference between version 3 and version 2:

At line 2 added 3 lines.
+ !Info
+ Below find screenshots of an example Kepler workflow using the RBNBToKepler2 actor and the resulting plots. This is junk "desk data"--the Campbell CR800 datalogger and sensors are set up and running on my desk. You can easily note when I switched from AC to solar near the beginning of the battery voltage plot. Sensors and the solar panel were/are occasionally arbitrarily moved about, though it was fairly infrequent (in the case of the panel, generally to better sit in sunlight). We had one cloudy day.
+ The program used to collect these data is also [posted below|TerrestrialUseCaseHardware#Datalogger Program].
Removed line 4
- Below find screenshots of an example RBNBToKepler2 workflow and the resulting plots. This is junk "desk data"--the Campbell CR800 datalogger and sensors are set up and running on my desk. You can easily note when I switched from AC to solar near the beginning of the battery voltage plot. Sensors and the solar panel were/are occasionally arbitrarily moved about, though it was fairly infrequent (in the case of the panel, generally to better sit in sunlight). We had one cloudy day.
Removed line 6
-
Lines 10-19 were replaced by lines 11-20
- | [Air Temp|RBNBSinkActorDesignAndAPI#Air Temp] | Campbell | Temp & RH Probe #1 | [CS215-L|http://www.campbellsci.com/cs215] | Deg C | inside Gill Radiation Shield
- | [Relative Humidity|RBNBSinkActorDesignAndAPI#Relative Humidity] | Campbell | Temp & RH Probe #1 | [CS215-L|http://www.campbellsci.com/cs215] | % | inside Gill Radiation Shield
- | [Battery Voltage|RBNBSinkActorDesignAndAPI#Battery Voltage] | Campbell | (12V Power Supply w/ Voltage Regulator) | ([PS100|http://www.campbellsci.com/ps100]) | Volts |
- | [Line Photosynthetic Photon Flux (PPF) 1|RBNBSinkActorDesignAndAPI#Line Photosynthetic Photon Flux (PPF) 1] | Apogee | Line Quantum Sensor #1 | [LQS70-10|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [1]
- | [Line PPF 2|RBNBSinkActorDesignAndAPI#Line PPF 2] | Apogee | Line Quantum Sensor #2 | [LQS70-10|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [1]
- | [Point PPF|RBNBSinkActorDesignAndAPI#Point PPF] | Apogee | Quantum Sensor | [QSO-SUN|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [#1] plot is mV. Sensor has standard calibration 5.00 µmol m^-2s^-1 per mV. Full sunlight is 2000µmol m^-2s^-1 (400mV). PPF = sensor output * 5.00 µmol m^-2s^-1
- | [Records|RBNBSinkActorDesignAndAPI#Records] | n/a | n/a | n/a |
- | [Wind Speed|RBNBSinkActorDesignAndAPI#Wind Speed] | Campbell | Anemometer | [014A-L|http://www.campbellsci.com/014a] | m/s |
- | [Volumetric Water Content (VWC) 1|RBNBSinkActorDesignAndAPI#Volumetric Water Content (VWC) 1] | Campbell | Reflectometer #1 | [CS616|http://www.campbellsci.com/cs616-l] | % | currently sitting on desk, not in soil
- | [VWC 2|RBNBSinkActorDesignAndAPI#VWC 2] | Campbell | Reflectometer #2 | [CS616|http://www.campbellsci.com/cs616-l] | % | currently sitting on desk, not in soil
+ | [Air Temp|TerrestrialUseCaseHardware#Air Temp] | Campbell | Temp & RH Probe #1 | [CS215-L|http://www.campbellsci.com/cs215] | Deg C | inside Gill Radiation Shield
+ | [Relative Humidity|TerrestrialUseCaseHardware#Relative Humidity] | Campbell | Temp & RH Probe #1 | [CS215-L|http://www.campbellsci.com/cs215] | % | inside Gill Radiation Shield
+ | [Battery Voltage|TerrestrialUseCaseHardware#Battery Voltage] | Campbell | (12V Power Supply w/ Voltage Regulator) | ([PS100|http://www.campbellsci.com/ps100]) | Volts |
+ | [Line Photosynthetic Photon Flux (PPF) 1|TerrestrialUseCaseHardware#Line Photosynthetic Photon Flux (PPF) 1] | Apogee | Line Quantum Sensor #1 | [LQS70-10|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [1]
+ | [Line PPF 2|TerrestrialUseCaseHardware#Line PPF 2] | Apogee | Line Quantum Sensor #2 | [LQS70-10|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [1]
+ | [Point PPF|TerrestrialUseCaseHardware#Point PPF] | Apogee | Quantum Sensor | [QSO-SUN|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [#1] plot is mV. Sensor has standard calibration 5.00 µmol m^-2s^-1 per mV. Full sunlight is 2000µmol m^-2s^-1 (400mV). PPF = sensor output * 5.00 µmol m^-2s^-1
+ | [Records|TerrestrialUseCaseHardware#Records] | n/a | n/a | n/a |
+ | [Wind Speed|TerrestrialUseCaseHardware#Wind Speed] | Campbell | Anemometer | [014A-L|http://www.campbellsci.com/014a] | m/s |
+ | [Volumetric Water Content (VWC) 1|TerrestrialUseCaseHardware#Volumetric Water Content (VWC) 1] | Campbell | Reflectometer #1 | [CS616|http://www.campbellsci.com/cs616-l] | % | currently sitting on desk, not in soil
+ | [VWC 2|TerrestrialUseCaseHardware#VWC 2] | Campbell | Reflectometer #2 | [CS616|http://www.campbellsci.com/cs616-l] | % | currently sitting on desk, not in soil
At line 40 added 83 lines.
+
+
+ !Datalogger program
+ This is the Campbell CRBasic program running on the CR800 doing the sampling.
+ allSensors.CR8:
+ {{{
+
+ 'CR800
+ 'Created by Short Cut (2.5)
+ '
+ 'Modified to fit my wiring. Also made other changes. Derik Barseghian 09.12.07
+ 'ie WARNING: don't trust the wiring diagrams Shortcut shows when you open this prog
+
+ 'Declare Variables and Units
+ Public Batt_Volt
+ Public VW
+ Public PA_uS
+ Public VW_2
+ Public PA_uS_2
+ Public lqs70(2)
+ Public qsosun
+ Public WS_ms
+ Public TRHData(2)
+ Public Rain_mm
+
+ Alias TRHData(1)=AirTC
+ Alias TRHData(2)=RH
+
+ Units Batt_Volt=Volts
+ Units PA_uS=uSec
+ Units PA_uS_2=uSec
+ Units lqs70=mV
+ Units qsosun=mV
+ Units WS_ms=meters/second
+ Units Rain_mm=mm
+ Units AirTC=Deg C
+ Units RH=%
+
+ 'Define Data Tables
+ DataTable(Table1,True,-1)
+ DataInterval(0,10,Min,10)
+ Minimum(1,Batt_Volt,FP2,False,False)
+ Average(1,VW,FP2,False)
+ Average(1,VW_2,FP2,False)
+ Average(1,lqs70(1),FP2,False)
+ Average(1,lqs70(2),FP2,False)
+ Average(1,qsosun,FP2,False)
+ Average(1,WS_ms,FP2,False)
+ Maximum(1,WS_ms,FP2,False,False)
+ Minimum(1,WS_ms,FP2,False,False)
+ Average(1,AirTC,FP2,False)
+ Sample(1,RH,FP2)
+ Totalize(1,Rain_mm,FP2,False)
+ EndTable
+
+ 'Main Program
+ BeginProg
+ Scan(30,Sec,1,0)
+ 'Default Datalogger Battery Voltage measurement Batt_Volt:
+ Battery(Batt_Volt)
+ 'CS616 Water Content Reflectometer measurements VW and PA_uS:
+ CS616(PA_uS,1,5,1,1,1,0)
+ VW=-0.0663+(-0.0063*PA_uS)+(0.0007*PA_uS^2)
+ 'CS616 Water Content Reflectometer measurements VW_2 and PA_uS_2:
+ CS616(PA_uS_2,1,6,2,1,1,0)
+ VW_2=-0.0663+(-0.0063*PA_uS_2)+(0.0007*PA_uS_2^2)
+ 'Generic Single-Ended Voltage measurements lqs70(1):
+ VoltSe(lqs70(1),2,mV2500,1,True,0,_60Hz,1.0,0.0)
+ 'Generic Single-Ended Voltage measurements qsosun:
+ VoltSE(qsosun,1,mV2500,2,True,0,_60Hz,1.0,0.0)
+ '014A Wind Speed Sensor measurement WS_ms:
+ PulseCount(WS_ms,1,1,2,1,0.8,0.447)
+ If WS_ms<0.457 Then WS_ms=0
+ 'CS215 Temperature & Relative Humidity Sensor (CSL) measurements AirTC and RH:
+ SDI12Recorder(AirTC,3,"0","M!",1,0)
+ 'TE525MM/TE525M Rain Gauge measurement Rain_mm:
+ PulseCount(Rain_mm,1,2,2,0,0.1,0)
+ 'Call Data Tables and Store Data
+ CallTable(Table1)
+ NextScan
+ EndProg
+
+ }}}

Back to Terrestrial Use Case Hardware, or to the Page History.