At line 2 added 3 lines. |
+ !Info |
+ Below find screenshots of an example Kepler workflow using the RBNBToKepler2 actor and the resulting plots. This is junk "desk data"--the Campbell CR800 datalogger and sensors are set up and running on my desk. You can easily note when I switched from AC to solar near the beginning of the battery voltage plot. Sensors and the solar panel were/are occasionally arbitrarily moved about, though it was fairly infrequent (in the case of the panel, generally to better sit in sunlight). We had one cloudy day. |
+ The program used to collect these data is also [posted below|TerrestrialUseCaseHardware#Datalogger Program]. |
Removed line 4 |
- Below find screenshots of an example RBNBToKepler2 workflow and the resulting plots. This is junk "desk data"--the Campbell CR800 datalogger and sensors are set up and running on my desk. You can easily note when I switched from AC to solar near the beginning of the battery voltage plot. Sensors and the solar panel were/are occasionally arbitrarily moved about, though it was fairly infrequent (in the case of the panel, generally to better sit in sunlight). We had one cloudy day. |
Removed line 6 |
- |
Lines 10-19 were replaced by lines 11-20 |
- | [Air Temp|RBNBSinkActorDesignAndAPI#Air Temp] | Campbell | Temp & RH Probe #1 | [CS215-L|http://www.campbellsci.com/cs215] | Deg C | inside Gill Radiation Shield |
- | [Relative Humidity|RBNBSinkActorDesignAndAPI#Relative Humidity] | Campbell | Temp & RH Probe #1 | [CS215-L|http://www.campbellsci.com/cs215] | % | inside Gill Radiation Shield |
- | [Battery Voltage|RBNBSinkActorDesignAndAPI#Battery Voltage] | Campbell | (12V Power Supply w/ Voltage Regulator) | ([PS100|http://www.campbellsci.com/ps100]) | Volts | |
- | [Line Photosynthetic Photon Flux (PPF) 1|RBNBSinkActorDesignAndAPI#Line Photosynthetic Photon Flux (PPF) 1] | Apogee | Line Quantum Sensor #1 | [LQS70-10|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [1] |
- | [Line PPF 2|RBNBSinkActorDesignAndAPI#Line PPF 2] | Apogee | Line Quantum Sensor #2 | [LQS70-10|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [1] |
- | [Point PPF|RBNBSinkActorDesignAndAPI#Point PPF] | Apogee | Quantum Sensor | [QSO-SUN|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [#1] plot is mV. Sensor has standard calibration 5.00 µmol m^-2s^-1 per mV. Full sunlight is 2000µmol m^-2s^-1 (400mV). PPF = sensor output * 5.00 µmol m^-2s^-1 |
- | [Records|RBNBSinkActorDesignAndAPI#Records] | n/a | n/a | n/a | |
- | [Wind Speed|RBNBSinkActorDesignAndAPI#Wind Speed] | Campbell | Anemometer | [014A-L|http://www.campbellsci.com/014a] | m/s | |
- | [Volumetric Water Content (VWC) 1|RBNBSinkActorDesignAndAPI#Volumetric Water Content (VWC) 1] | Campbell | Reflectometer #1 | [CS616|http://www.campbellsci.com/cs616-l] | % | currently sitting on desk, not in soil |
- | [VWC 2|RBNBSinkActorDesignAndAPI#VWC 2] | Campbell | Reflectometer #2 | [CS616|http://www.campbellsci.com/cs616-l] | % | currently sitting on desk, not in soil |
+ | [Air Temp|TerrestrialUseCaseHardware#Air Temp] | Campbell | Temp & RH Probe #1 | [CS215-L|http://www.campbellsci.com/cs215] | Deg C | inside Gill Radiation Shield |
+ | [Relative Humidity|TerrestrialUseCaseHardware#Relative Humidity] | Campbell | Temp & RH Probe #1 | [CS215-L|http://www.campbellsci.com/cs215] | % | inside Gill Radiation Shield |
+ | [Battery Voltage|TerrestrialUseCaseHardware#Battery Voltage] | Campbell | (12V Power Supply w/ Voltage Regulator) | ([PS100|http://www.campbellsci.com/ps100]) | Volts | |
+ | [Line Photosynthetic Photon Flux (PPF) 1|TerrestrialUseCaseHardware#Line Photosynthetic Photon Flux (PPF) 1] | Apogee | Line Quantum Sensor #1 | [LQS70-10|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [1] |
+ | [Line PPF 2|TerrestrialUseCaseHardware#Line PPF 2] | Apogee | Line Quantum Sensor #2 | [LQS70-10|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [1] |
+ | [Point PPF|TerrestrialUseCaseHardware#Point PPF] | Apogee | Quantum Sensor | [QSO-SUN|http://www.apogeeinstruments.com/quantumsensor_specsheets.htm] | mV | [#1] plot is mV. Sensor has standard calibration 5.00 µmol m^-2s^-1 per mV. Full sunlight is 2000µmol m^-2s^-1 (400mV). PPF = sensor output * 5.00 µmol m^-2s^-1 |
+ | [Records|TerrestrialUseCaseHardware#Records] | n/a | n/a | n/a | |
+ | [Wind Speed|TerrestrialUseCaseHardware#Wind Speed] | Campbell | Anemometer | [014A-L|http://www.campbellsci.com/014a] | m/s | |
+ | [Volumetric Water Content (VWC) 1|TerrestrialUseCaseHardware#Volumetric Water Content (VWC) 1] | Campbell | Reflectometer #1 | [CS616|http://www.campbellsci.com/cs616-l] | % | currently sitting on desk, not in soil |
+ | [VWC 2|TerrestrialUseCaseHardware#VWC 2] | Campbell | Reflectometer #2 | [CS616|http://www.campbellsci.com/cs616-l] | % | currently sitting on desk, not in soil |
At line 40 added 83 lines. |
+ |
+ |
+ !Datalogger program |
+ This is the Campbell CRBasic program running on the CR800 doing the sampling. |
+ allSensors.CR8: |
+ {{{ |
+ |
+ 'CR800 |
+ 'Created by Short Cut (2.5) |
+ ' |
+ 'Modified to fit my wiring. Also made other changes. Derik Barseghian 09.12.07 |
+ 'ie WARNING: don't trust the wiring diagrams Shortcut shows when you open this prog |
+ |
+ 'Declare Variables and Units |
+ Public Batt_Volt |
+ Public VW |
+ Public PA_uS |
+ Public VW_2 |
+ Public PA_uS_2 |
+ Public lqs70(2) |
+ Public qsosun |
+ Public WS_ms |
+ Public TRHData(2) |
+ Public Rain_mm |
+ |
+ Alias TRHData(1)=AirTC |
+ Alias TRHData(2)=RH |
+ |
+ Units Batt_Volt=Volts |
+ Units PA_uS=uSec |
+ Units PA_uS_2=uSec |
+ Units lqs70=mV |
+ Units qsosun=mV |
+ Units WS_ms=meters/second |
+ Units Rain_mm=mm |
+ Units AirTC=Deg C |
+ Units RH=% |
+ |
+ 'Define Data Tables |
+ DataTable(Table1,True,-1) |
+ DataInterval(0,10,Min,10) |
+ Minimum(1,Batt_Volt,FP2,False,False) |
+ Average(1,VW,FP2,False) |
+ Average(1,VW_2,FP2,False) |
+ Average(1,lqs70(1),FP2,False) |
+ Average(1,lqs70(2),FP2,False) |
+ Average(1,qsosun,FP2,False) |
+ Average(1,WS_ms,FP2,False) |
+ Maximum(1,WS_ms,FP2,False,False) |
+ Minimum(1,WS_ms,FP2,False,False) |
+ Average(1,AirTC,FP2,False) |
+ Sample(1,RH,FP2) |
+ Totalize(1,Rain_mm,FP2,False) |
+ EndTable |
+ |
+ 'Main Program |
+ BeginProg |
+ Scan(30,Sec,1,0) |
+ 'Default Datalogger Battery Voltage measurement Batt_Volt: |
+ Battery(Batt_Volt) |
+ 'CS616 Water Content Reflectometer measurements VW and PA_uS: |
+ CS616(PA_uS,1,5,1,1,1,0) |
+ VW=-0.0663+(-0.0063*PA_uS)+(0.0007*PA_uS^2) |
+ 'CS616 Water Content Reflectometer measurements VW_2 and PA_uS_2: |
+ CS616(PA_uS_2,1,6,2,1,1,0) |
+ VW_2=-0.0663+(-0.0063*PA_uS_2)+(0.0007*PA_uS_2^2) |
+ 'Generic Single-Ended Voltage measurements lqs70(1): |
+ VoltSe(lqs70(1),2,mV2500,1,True,0,_60Hz,1.0,0.0) |
+ 'Generic Single-Ended Voltage measurements qsosun: |
+ VoltSE(qsosun,1,mV2500,2,True,0,_60Hz,1.0,0.0) |
+ '014A Wind Speed Sensor measurement WS_ms: |
+ PulseCount(WS_ms,1,1,2,1,0.8,0.447) |
+ If WS_ms<0.457 Then WS_ms=0 |
+ 'CS215 Temperature & Relative Humidity Sensor (CSL) measurements AirTC and RH: |
+ SDI12Recorder(AirTC,3,"0","M!",1,0) |
+ 'TE525MM/TE525M Rain Gauge measurement Rain_mm: |
+ PulseCount(Rain_mm,1,2,2,0,0.1,0) |
+ 'Call Data Tables and Store Data |
+ CallTable(Table1) |
+ NextScan |
+ EndProg |
+ |
+ }}} |